The effect of real network phase disturbances on the calculation of IEC 61000-4-30 parameters
Date
2014Author
Rens, Johan
De Kock, Jan
Van Wyk, Willie
Van Zyl, Jacobus
Metadata
Show full item recordAbstract
Real life network dynamic phenomena are used to demonstrate how the calculation of IEC 61000-4-30 parameters can be affected. The voltage frequency can change instantaneously at a point in the network due to a shift in the position of zero crosses when large reactive power changes occur. Pseudo voltage swells can be recorded and spectral leakage incurred. It is proposed that a 10/12-cycle block value for frequency is used in addition to the IEC 61000-4-30 10-second values
URI
http://hdl.handle.net/10394/20264https://ieeexplore.ieee.org/stamp/stamp.jsp?arnumber=6842886