Sensitivity of static energy meter reading errors to changes in non-sinusoidal load conditions
Date
2019Author
Marais, Z.
Rens, J.
Van den Brom, H.E.
Rietveld, G.
Van Leeuwen, R.
Metadata
Show full item recordAbstract
Previous studies regarding static energy meter
errors under non-sinusoidal load conditions have shown that these
meters can produce erroneous readings. This paper describes an
investigation done using loads consisting of a commercial lighting
dimmer in combination with either a resistive heater or an array
of various energy-saving lamps. Dimmer impedance and phase
firing angle were gradually adjusted to change load conditions.
Several meters showed dramatic variations in metering error
under different load conditions. In the most extreme case,
metering errors ranged from five times the energy consumed by
the load to registering almost no energy. Though perhaps not
typically found in households, the load combinations used in this
study were able to highlight sensitivities of different static energy
meters to changes in load conditions
URI
http://hdl.handle.net/10394/33663https://ieeexplore.ieee.org/abstract/document/8872006
https://doi.org/10.1109/EMCEurope.2019.8872006